Gw-instek PEL-2000 Series Programming User Manual Manual do Utilizador Página 129

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 170
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 128
COMMAND DETAILS
129
Example
:STAT:QUES:NTR 5
OC (Bit 1) and OP (Bit 3)
are set as negative
transitions.
:STAT:CHAN:PTR 2
OV (Bit 2) is set as a
positive transition.
Query Syntax
:STATus:QUEStionable:NTRansition/PTRansition?
<NR1>
Return Parameter
<NR1>
Event
<NR1>
Event
1
OC
16
OT
2
OV
32
G/N
4
OP
64
UVP
8
RV
128~65535
Not used
Query Example
:STAT:QUES:NTR?
4
Returns which
conditions (OP) have
negative transitions.
:STATus:PREset
Channel Specific
Command
Description
The status preset command resets the Enable
registers and NTR/PTR registers from the Channel
Status and Questionable Status Register groups.
Preset
Register
Preset
Channel Status Enable
All bits set to 1
Channel Status PTR
All bits set to 1
Channel Status NTR
All bits set to 0
Questionable Status Enable
All bits set to 0
Questionable Status PTR
All bits set to 1
Questionable Status NTR
All bits set to 0
Syntax
:STATus:PREset
Example
:STAT:PRE
Vista de página 128